Carrier 19DK (DM) series fault code and fault handling method

文章附图

Carrier 19DK (DM) series fault code and fault handling method



category


Code


Description / fault situation


Possible cause/countermeasure

Timer


0-15


From the next start time (already divided into units)


It is forbidden to start in 15 minutes or 3 minutes. The timer is not completed.

Startup state


20


Start the freezer on the S/D board


After the control power is sent or after the POR, the LCD displays a countdown of three minutes, and the code of the start state of the freezer will appear.

Startup state


twenty one


Start the freezer from the remote control switch


After the control power is sent or after the POR, the LCD displays a countdown of three minutes, and the code of the start state of the freezer will appear.

Startup state


twenty two


Start the freezer on the expansion monitor (ESP)


After the control power is sent or after the POR, the LCD displays a countdown of three minutes, and the code of the start state of the freezer will appear.

Startup state


twenty three


Waiting for the start signal from the main freezer


After the control power is sent or after the POR, the LCD displays a countdown of three minutes, and the code for the start state of the freezer will appear.

Startup state


twenty four


The sub-compressor is set at the position of indefinite operation (DISABLED)


The DIP SWITCH that sets the sub-compressor not to operate is set to the ON position.

Startup state


25


Recycling operation has not started


The ice water or brine effluent temperature is too low to meet the conditions for recirculation start-up (ice water temperature ≤ 5 °F (2-8 ° C) above the set point.

Startup state


26


Startup process in progress


Perform pre-start inspection, water flow and oil pressure are being established.

Operational state


28


Capacity control


The main unit is operating normally under temperature control

Operational state


29


Ramp Loading Capacity Control


Ice water effluent temperature reduction rate is controlled by Ramp loading

Operational state


30


Power demand limit capacity control


Compressor motor current power demand set point - confirm that the motor current correction point is correct

Operational state


35


Motor temperature priority control


The motor temperature >200°F (93.3°C) confirms the motor temperature and the resistance of the temperature sensor.

Operational state


36


Refrigerant temperature priority control


Refrigerant temperature ≤ 1°F above the set point (0.56°C)

Operational state


37


Exhaust frequency is too frequent


Please see the location of the AUTO, the exhaust cycle is too frequent / inside the description

Fault state before start


40


Motor coil temperature is too high


The motor temperature is >190°F (87.8°C). If the temperature is <190°F (87.8°C), press RE SET to confirm the resistance of the temperature sensor.

Fault state before start


41


Started more than 8 times in the past 12 hours


Subject to 8 start/12 hour counter limits, press the RESET button to force a start.

Fault state before start


42


Cooling water volume cannot be established


Check the water pump, power supply and pilot wire appliance, check the water flow switch, check the water valve and check if there is air in the water view.

Fault state before start


43


Ice water volume cannot be established


Check the water pump, power supply and pilot wire appliance, check the water flow switch, check the water valve and check if there is air in the water view.



Fault state before start




44




Oil pump pressure switch problem




When the oil pump is not open, the oil pressure switch contact is the path (CLOSED), check the contact and switch settings.

Fault state before start


45


Temperature sensor (Sensor) reading out of range


Perform a control test to check if the setpoint potentiometer is damaged, if the temperature sensing rod is open or shorted, and confirm the contact and switch setting.

Fault state before start


46


The oil pressure switch is not connected within 15 seconds after the oil pump is started (cannot be established)


Check the oil pump power, oil level and oil pressure switch settings to check if the oil filter is too dirty.

Fault state before start


48


Voltage too high / low


The control center supply voltage <94.3VAC or >135.5VAC lasts for more than a minute. Check the control center transformer, circuit load, if the voltage is indeed too low, you should inform the power company and try to improve. Please refer to I/OBoard replacement.

Host trip status


56


The secondary compressor is not normal (dual-type freezer)


The safety switch of the sub-compressor exceeds the limit value (press the sub-compressor status button to display the fault code)

Host trip status


60


Compressor exhaust temperature >220°F


Check the exhaust temperature immediately, measure the resistance of the sense bar, check the flow and temperature of the cooling water, check the temperature of the tank, and check if the condenser leaks air or moisture.

Host trip status


61


Evaporator refrigerant temperature <limit value


Check the refrigerant temperature, the temperature of the temperature bar, and check the amount of refrigerant.

Host trip status


62


Motor coil temperature >220°F (104°C) 190°F (88°C) reset


Check the motor temperature immediately, measure the resistance of the temperature sensing bar and the connector of the junction box on the compressor, and check if the motor cooling system is not well cooled.

Host trip status


63


Thrust bearing temperature >220°F (104°C)


Check the tank temperature, check the oil cooler water volume and solenoid valve, check the oil heater temperature switch setting value, measure the temperature sensing rod resistance value and the connector of the junction box on the compressor. If there is no abnormality in the above items, check the head shaft. And thrust bearings.

Host trip status


64


Temperature sensing rod (SENSOR) reading is out of range


Perform a control test to check if the setpoint potentiometer is damaged, if the temperature sensing rod is shorted or shorted, and confirm the resistance of the temperature sensing rod. Check that the motor current signal disappears when the compressor starts. Check the diffusion wall feedback potentiometer calibration point.

Host trip status


65


Oil pressure <limit value


Check the oil pump power supply, oil level oil pressure switch setting value, check if the oil filter net is too dirty, confirm whether there is foaming of the frozen oil at startup, if any, slow down the rate of Ramp Loading

Host trip status


66


Motor overload relay trip


Check the motor overload relay delay oil only and set value (do not be corrected in the field), check the motor current demand correction point, check the compressor motor starter other protection equipment (such as: under-phase, grounding protection, etc.) and then start Check the motor for the same open circuit or ground protection before

Host trip status


67


Instant power outage


The control center voltage <57.5VAC lasts for more than one-sixth of a second and press the RESET button to restart.

Host trip status


68


Voltage is too low


The control center power supply voltage <94.3VAC lasts for more than one minute. Check the control center transformer, circuit load, if the voltage is indeed too low, you should inform the power company and try to improve

Host trip status


69


The voltage is too high


The control center supply voltage >135.7VAC lasts for more than a minute. Check the control center voltage and transformer. If the voltage is indeed too high, notify the power company and try to improve it.

Host trip status


70


Insufficient ice water flow


Check the pilot relay, check the pump power supply, check the water flow switch and the water stop valve

Host trip status


71


Insufficient flow of condensate


Check the pilot relay, check the pump power supply, check the water flow switch and the water stop valve

Host trip status


72


Shorted jumper (Jumper)


Check the short circuit of the ground

Host trip status


73


Condenser pressure is too high


Check condenser pressure switch setting, check condensate flow and temperature, check if condenser copper tube is dirty

Host trip status


74


The starter cannot be switched to the delta connection


Check the starter, check the RUN contact, check the configuration of the DIP switch and whether the starter type matches

Host trip status


75


Motor acceleration time is too long


Check if the door is closed at startup, confirm the starter switching time, and check the door linkage. Check that the configuration of the dial and the type of starter match.

Host trip status


76


Dip switch configuration error


Confirm the position of the dip switch setting

Host trip status


77


The “Run/Switch” contact can be turned off when the machine is stopped.


Check the running contact, check the 1CR relay, and check if the starter contact is stuck.

Host trip status


78


Manual shutdown


When the L/R switch is placed in the "REMOTE" position, the "STOP" button is pressed and reset.

Host trip status


79


Alternate safety protector action


Check the alternate safety protector contacts and check that the alternate safety protector is functioning properly.

Host trip status


80


Recirculation operation with motor current >65% RLA


Check the ice water, condensate flow rate and temperature are normal, check the resistance value of the ice water / brine water temperature sensor, check the motor current correction point is correct, check the door motor and connecting rod.

Host trip status


81


Communication interruption


The communication tube of the freezer control center and ESP has not been established or established and is interrupted for more than 15 seconds. Please see the ESP operating instructions

Host trip status


85


Sub Compressor Diffusion Wall Abnormal (Double Model


The position of the secondary compressor diffuser wall is not within the allowable range. Please check the action of the solenoid valve.

Host trip status


87


Starter RUN contact open circuit during freezer operation


Check the starter, check the RUN contact, and check the field wiring connector.

Host trip status


88


The sub-compressor surge protection function makes the freezer jump


Check the body for leaks or the copper tube is too dirty. Check the air guide door / door motor and connecting rod.



——


Ice water temperature is too high (freezer is running)


The thermostat set point is too high - reset the thermostat.





Capacity Override or freezing load is too large (the freezer is running at the rated tonnage)--Check the fault number to check if the outside air leaks into the house.





The condenser temperature is too high--check the condensate flow rate, check the condensate temperature; check the cooling tower operation, check for air leakage or water leakage, and check if the condenser copper tube is too dirty.





The refrigerant is too low - check leaks and leaks, add refrigerant and adjust the amount of perfusion.





Short circuit of water flow in the water tank - check the partition plate and gasket for leaks.





The door cannot be opened - check the door motor for damage and replace it if it is damaged.





The door cannot be fully opened - confirm that the capacity control switch is in the "AUTO" position. If the "INC" door still cannot be opened, please confirm if the freezing load is too large (see above). Check the resistance of the ice water or brine temperature bar. Check the door linkage, check the start switch in the door, and check that the sensor is connected to the appropriate terminal.





The sub-compressor is not started as required (dual compressor freezer) - check the status of the sub-compressor (STATUS) to check if the conditions for starting the sub-compressor are met.



——


Ice water or brine temperature is too low (freezer is running)


The door cannot be closed - confirm that the capacity control switch is in the "AUTO" position. Check the resistance value of the ice water or salt water temperature sensor, check the door connecting rod, check if the door motor is damaged, replace it if it is damaged, and check if the sensor is connected to the appropriate terminal.





The temperature sensing rod is damaged, check the resistance of the temperature sensing rod.





The evaporator refrigerant temperature switch is not set properly (in the case of salt water). Check the refrigerant temperature set point.





The thermostat set point is too low to reset the thermostat.



——


Ice water temperature fluctuates up and down; the door has a hunting phenomenon


The deadband is too narrow (flow or temperature is unstable) and the pullband configuration Deadband is set to 2°F (1°C).





The Proprtional Band is too narrow (flow or temperature instability) and the switch configuration Proporti onal Band is set to 15°F (8.3°C)





The door connecting rod is loose - adjust the door connecting rod.





Door motor damage - replace the door motor.





Damage to the temperature sensing rod - replace the temperature sensing rod.



——


Tank temperature is too low


The amount of water in the oil cooler is too large - adjust the amount of water





The temperature switch set point is not appropriate or damaged - the voltage between the temperature switch terminals is measured during the adjustment. If the contacts are not connected, the temperature switch should be replaced.





The oil heater is damaged. If the indicator power is turned on but the heater is not heated, check if the heater is open or shorted and replace if necessary.





——




Tank temperature is too high




The oil cooler is too small - turn on the adjusted water volume.





Temperature switch set point is incorrect - readjust the set point





The oil cooler solenoid valve does not operate normally. Check the action of the solenoid valve coil and check the valve body. If the filter is dirty, clean it and install a 20 mesh (MESH) filter in front of the valve body.





The oil cooler coil is too dirty, clean the coil and replace if necessary.



——


The refrigerant has disappeared a lot


The number of operation of the eliminator pump is too frequent, and the part of the ejector that operates too frequently in the "AUTO" position



——


The ejector does not operate in the "AUTO" position


Under normal circumstances, the pressure of the eliminator must be within 2-4Psi (14-28Kpa) of the condenser pressure, and the eliminator pump will run. Check the pressure gauge reading for the operation of the exhaust system.





The fuse is blown. (On some hosts) Check the 15 amp protection in the ejector switch boxcarrier-30hxc-screw-chiller-328x328.jpg